Revision August 2008, 03VE, SW V2.04 1-1 Chapter 1 Introduction The AC motor drive should be kept in the shipping carton or crate before installatio

Strany 3

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-51Control mode VF VFPG SVC Factory setting: 0.50 Settings 0.0

Strany 4 - Preface

Chapter 4 Parameters| 4-52 Revision August 2008, 03VE, SW V2.04 Control mode VF VFPG SVC Settings 230V series 0.1 to 255.0V Factory Setting:

Strany 5 - WARNING!

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-53Fcmd>Fmin Fstart>Fmin NOYESYESfstart=Fstart NOfstart=FminFl

Strany 6

Chapter 4 Parameters| 4-54 Revision August 2008, 03VE, SW V2.04 Fcmd>Fmin Fstart>Fmin NOYESYESfstart=Fstart NOfstart=FminFlow=0Flow=0YESH=FcmdY

Strany 7

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-55min. frequency, it will run with lower limit frequency. The upper

Strany 8

Chapter 4 Parameters| 4-56 Revision August 2008, 03VE, SW V2.04  The Acceleration/Deceleration Time 1, 2, 3, 4 are selected according to the Multi-

Strany 9

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-5701-27  S-curve for Deceleration Arrival Time 2 Unit: 0.1/0.01C

Strany 10 - Chapter 1 Introduction

Chapter 4 Parameters| 4-58 Revision August 2008, 03VE, SW V2.04 2 Fmin (4th output frequency setting)  When the frequency is less than Fmin (Pr.

Strany 11 - 1.1 Receiving and Inspection

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-59Group 2 Digital Input/Output Parameters 02-00 2-wire/3-wire Ope

Strany 12 - 367T037V23A2

Chapter 4 Parameters| 4-60 Revision August 2008, 03VE, SW V2.04 02-04 Multi-Function Input Command 4 (MI4) Factory Setting: 402-05 Multi-Fun

Strany 13 - 1.2.1 Ambient Conditions

Chapter 1 Introduction| 1-2 Revision August 2008, 03VE, SW V2.041.1 Receiving and Inspection This VFD-VE AC motor drive has gone through rigorous qu

Strany 14 - Air Flow

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-61Control Mode Settings VF VFPG SVC FOCPG TQRPG13: cancel the se

Strany 15 - 1.2.2 Remove Keypad

Chapter 4 Parameters| 4-62 Revision August 2008, 03VE, SW V2.04 Settings Functions Descriptions 0 No Function 1 Multi-step speed command 1/multi

Strany 16 - 1.2.3 Remove Front Cover

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-63Settings Functions Descriptions optimal accel./decel. time 01/0

Strany 17 - 1.2.4 Lifting

Chapter 4 Parameters| 4-64 Revision August 2008, 03VE, SW V2.04 Settings Functions Descriptions 32 Middle torque bias (by Pr.07-30) The middle torq

Strany 18 - 1.3 Dimensions

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-65Settings Functions Descriptions 35 Enable position control Whe

Strany 19 - Chapter 1 Introduction

Chapter 4 Parameters| 4-66 Revision August 2008, 03VE, SW V2.04 Settings Functions Descriptions MI=d1Run/Stop111010 =102corresponds to Pr.04-241100

Strany 20

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-67Settings Functions Descriptions 42 Serial position input When

Strany 21

Chapter 4 Parameters| 4-68 Revision August 2008, 03VE, SW V2.04 02-08  The Acceleration/Deceleration Speed of the UP/DOWN Key with Constant Speed Un

Strany 22

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-69 Factory Setting: 102-13  Multi-function Output 3 (MO1)

Strany 23

Chapter 4 Parameters| 4-70 Revision August 2008, 03VE, SW V2.04 Control Mode Settings VF VFPG SVC FOCPG TQRPG12: Mechanical brake release (Pr.02-3

Strany 24 - CAUTION!

Chapter 1 Introduction| Revision August 2008, 03VE, SW V2.04 1-31.1.3 Series Number Explanation 367T037V23A2Production numberPro

Strany 25 - 2.1 Wiring

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-71Settings Functions Descriptions 4 Desired Frequency Attained 2

Strany 26 - 0~10VDC/2mA

Chapter 4 Parameters| 4-72 Revision August 2008, 03VE, SW V2.04 Settings Functions Descriptions 21 Over-voltage Warning Active when the over-voltag

Strany 27 - 2.2 External Wiring

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-73Settings Functions Descriptions 40 Speed Attained (including ze

Strany 28 - 2.3 Main Circuit

Chapter 4 Parameters| 4-74 Revision August 2008, 03VE, SW V2.04 Settings Functions Descriptions 50 Reserved Example of crane function 02-3102-31F

Strany 29

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-75If Pr02-11=1 and Pr02-15=1, Relay 1 RA-RC is open when the drive

Strany 30 - DC reactor

Chapter 4 Parameters| 4-76 Revision August 2008, 03VE, SW V2.04 TRG[00-04=01]02-13=1802-14=1702-16=502-17=3[02-06=23]Display valueCounter Trigger(out

Strany 31 - Brake resistor(optional

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-7702-11~14=302-11~14=4Fcmd=60Hz02-19=10Hz02-20=2Hz02-21=40Hz02-22=2

Strany 32 - 2.3.2 Main Circuit Terminals

Chapter 4 Parameters| 4-78 Revision August 2008, 03VE, SW V2.04 Settings 0~100%  When output current is higher than Pr.02-32, it will activate

Strany 33 - 2.4 Control Terminals

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-79Group 3 Analog Input/Output Parameters 03-00 Analog Input 1 (AVI

Strany 34 - Internal CircuitDCM

Chapter 4 Parameters| 4-80 Revision August 2008, 03VE, SW V2.04 Positive torqueReverse03-00~02=7Positive torque limit03-00~02=8Negative torque limit0

Strany 35

Chapter 1 Introduction| 1-4 Revision August 2008, 03VE, SW V2.0415-30HP/11-22kW (Frame D) 40-100HP/30-75kW (Frame E) Frame Power range Models

Strany 36 - AVI circuit

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-81Control mode VF VFPG SVC FOCPG TQRPG Factory setting: 0 Setti

Strany 37 - AVI/ACI/AUI

Chapter 4 Parameters| 4-82 Revision August 2008, 03VE, SW V2.04 03-14  Analog Input Delay Time (ACI) Unit: 0.0103-15  Analog Input Delay Time (A

Strany 38

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-83 Settings 0 to 19 Settings Functions Descriptions 0 Output

Strany 39

Chapter 4 Parameters| 4-84 Revision August 2008, 03VE, SW V2.04 Settings Functions Descriptions 19 Pulse frequency command Max. frequency Pr.01-00

Strany 40 - 3.1 Digital Keypad KPV-CE01

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-85Group 4 Multi-Step Speed Parameters 04-00 1st Step Speed Frequ

Strany 41

Chapter 4 Parameters| 4-86 Revision August 2008, 03VE, SW V2.04 Settings 0 to 65535  Please refer to the explanation of Pr.02-00 to Pr.02-06.

Strany 42

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-87Group 5 Motor Parameters 05-00 Motor Auto Tuning Control mode S

Strany 43

Chapter 4 Parameters| 4-88 Revision August 2008, 03VE, SW V2.04 05-01 Full-load Current of Motor 1 Control mode VF VFPG SVC FOCPG TQRPG Factory

Strany 44 - KPV-CEO1

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-89 05-06 Rotor Resistance R1 of Motor 1 Unit: 0.00105-07 Rr of M

Strany 45

Chapter 4 Parameters| 4-90 Revision August 2008, 03VE, SW V2.04  When output frequency reaches Y-connection/Δ −connection switch frequency, drive w

Strany 46 - KPV-CE01

Chapter 1 Introduction| Revision August 2008, 03VE, SW V2.04 1-5 Air Temperature: -10 ~ +40°C (14 ~ 122°F) Relative Humidity: &

Strany 47 - 3.2.2 Trial Run

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-91Y-connection outputPr.02-11~14=31Y-connection confirmation inputP

Strany 48

Chapter 4 Parameters| 4-92 Revision August 2008, 03VE, SW V2.04 05-16 Number of Motor Poles 2 Control mode VF VFPG SVC FOCPG TQRPG Factory settin

Strany 49

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-93 05-24  Torque Compensation Gain Unit: 1Control mode VF VFPG

Strany 50 - Chapter 4 Parameters

Chapter 4 Parameters| 4-94 Revision August 2008, 03VE, SW V2.04  Pr.05-26 to Pr.05-28 are used to set allowable slip level/time and over slip treat

Strany 51 - Group 0 System Parameters

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-95Group 6 Protection Parameters 06-00 Low Voltage Level Unit: 0

Strany 52

Chapter 4 Parameters| 4-96 Revision August 2008, 03VE, SW V2.04 06-02 Phase-loss Protection Control mode VF VFPG SVC FOCPG TQRPG Factory Settin

Strany 53 - Group 1 Basic Parameters

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-97Over-Current Detection Level06-04Output CurrentOutput FrequencyOv

Strany 54

Chapter 4 Parameters| 4-98 Revision August 2008, 03VE, SW V2.04 Settings 10 to 250% 06-08 Over-torque Detection Time (OT1) Unit: 0.1Control mo

Strany 55

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-995%Pr.06-07, Pr.06-10Pr.06-08, 06-11current 06-12  Current Limi

Strany 56

Chapter 4 Parameters| 4-100 Revision August 2008, 03VE, SW V2.04  The parameter is set by the output frequency, current and operation time of the d

Strany 57

Chapter 1 Introduction| 1-6 Revision August 2008, 03VE, SW V2.04CAUTION! 1. Operating, storing or transporting the AC motor drive outside these con

Strany 58

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-101Control Mode Settings VF VFPG SVC FOCPG TQRPG0: No fault ○ ○

Strany 59

Chapter 4 Parameters| 4-102 Revision August 2008, 03VE, SW V2.04 Control Mode Settings VF VFPG SVC FOCPG TQRPG52: Password error (PcodE) ○ ○ ○

Strany 60

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-103Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6Fault code current Volt. OL

Strany 61 - Group 5 Motor Parameters

Chapter 4 Parameters| 4-104 Revision August 2008, 03VE, SW V2.04 Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6Fault code current Volt. OL SYS FBK EXI CE27:

Strany 62

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-105Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6Fault code current Volt. OL

Strany 63

Chapter 4 Parameters| 4-106 Revision August 2008, 03VE, SW V2.04 Settings 0.0 to 100.0%  It is used to set the PTC level, and the corresponding va

Strany 64

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-107Group 7 Special Parameters 07-00  Software Brake Level Unit:

Strany 65 - Group 7 Special Parameters

Chapter 4 Parameters| 4-108 Revision August 2008, 03VE, SW V2.04 ONOFF01-09Output frequencyRun/StopTimeDC Braking TimeDC Braking Timeduring StoppingM

Strany 66 - 0.0~100.0% 20.0

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-109 Settings 0.1 to 5.0 sec  If the duration of a power loss is

Strany 67 - -100.0~+100.0% 0.0

Chapter 4 Parameters| 4-110 Revision August 2008, 03VE, SW V2.04 TimeB.B.output current AInput B.B. signalStop output voltageDisable B.B. signalWait

Strany 68

Chapter 1 Introduction| Revision August 2008, 03VE, SW V2.04 1-715-30HP/11-22kW (Frame D) 40-100HP/30-75kW (Frame E) 1.2.3 Re

Strany 69

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-111 07-10 Base Block Speed Search Control mode VF VFPG SVC FOCPG

Strany 70

Chapter 4 Parameters| 4-112 Revision August 2008, 03VE, SW V2.04  In PG control mode, the AC motor drive will execute the speed search function aut

Strany 71

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-11307-14NOTEDC BUS voltageit doesn't need multi-function termi

Strany 72

Chapter 4 Parameters| 4-114 Revision August 2008, 03VE, SW V2.04 07-15  Dwell Time at Accel. Unit: 0.01Control mode VF VFPG SVC FOCPG Factor

Strany 73

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-11507-20  Torque Command Unit: 0.1Control mode TQRPG Fact

Strany 74 - Group 11 Advanced Parameters

Chapter 4 Parameters| 4-116 Revision August 2008, 03VE, SW V2.04 07-26 00-2007-2500-2007-2607-2507-24=1 07-24=1torquetorquetorquefrequencyfrequencyfr

Strany 75 - 4.2.2 Version 2.04

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-11707-28  Torque Offset Setting Unit: 0.1Control mode SVC FOCPG

Strany 76

Chapter 4 Parameters| 4-118 Revision August 2008, 03VE, SW V2.04 Positive torqueNegative torquespeed06-12 current limit06-12 current limit06-12 curre

Strany 77

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-119Group 8 High-function PID Parameters 08-00  Input Terminal for

Strany 78

Chapter 4 Parameters| 4-120 Revision August 2008, 03VE, SW V2.04 08-03  Derivative Control (D) Unit: 0.01Control mode VF VFPG SVC FOCPG Fact

Strany 79

Chapter 1 Introduction| 1-8 Revision August 2008, 03VE, SW V2.0415-30HP/11-22kW (Frame D) 40-100HP/30-75kW (Frame E) 1.2.4 Lifting Please carry onl

Strany 80

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-121Inp ut Selectionof the PID Fee dbackPID CancelledPID Freq. out p

Strany 81

Chapter 4 Parameters| 4-122 Revision August 2008, 03VE, SW V2.04 Control mode VF VFPG SVC FOCPG Factory Setting: 0.0 Settings 0.0 to 3600.0 se

Strany 82

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-123 08-1108-1008-120HzSleep FunctionFrequency commandactua

Strany 83 - New parameters 08-21~08-99

Chapter 4 Parameters| 4-124 Revision August 2008, 03VE, SW V2.04 +-08-25 & 08-2608-27PI08-29 & 08-3008-32 & 08-33Limit ++PID output fr

Strany 84

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-125MotorEncoderPG2driveline speed feedbackline speedcommandAI or co

Strany 85

Chapter 4 Parameters| 4-126 Revision August 2008, 03VE, SW V2.04 08-22 Wind Mode Control mode VF VFPG SVC FOCPG TQRPG Factory Setting: 0 Settings

Strany 86

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-127Control mode VF VFPG SVC FOCPG TQRPG Factory Setting: 0 Sett

Strany 87

Chapter 4 Parameters| 4-128 Revision August 2008, 03VE, SW V2.04 Control mode VF VFPG SVC FOCPG TQRPG Factory Setting: 50.0 Settings 0.0 to 1000.0

Strany 88

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-129 3 Pulse input (Pr.08-40) 4 DFM-DCM pulse input (Pr.02-18

Strany 89

Chapter 4 Parameters| 4-130 Revision August 2008, 03VE, SW V2.04 Control mode VF VFPG SVC FOCPG TQRPG Factory Setting: 0.0 Settings 0.0 to 3000.

Strany 90

Chapter 1 Introduction| Revision August 2008, 03VE, SW V2.04 1-9Step 3 Step 4 1.3 Dimensions

Strany 91 - Unit: 1

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-131the path when Pr.08- 42 is set to 1Driverth e pa th when Pr.08-

Strany 92 - 00-0800-08

Chapter 4 Parameters| 4-132 Revision August 2008, 03VE, SW V2.04 Control mode VF VFPG SVC FOCPG TQRPG Factory Setting: 1 Settings 1 to 10000ppr

Strany 93

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-133 Settings 0.0~100.0% (according to Pr.08-26) 08-57 Frequency

Strany 94

Chapter 4 Parameters| 4-134 Revision August 2008, 03VE, SW V2.04 Control mode VF VFPG SVC FOCPG Factory Setting: 100 Settings 0~100%  The corr

Strany 95

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-135 Settings 0.00~100.00 sec 08-71 | 08-75 Reserved 08-76 Source

Strany 96

Chapter 4 Parameters| 4-136 Revision August 2008, 03VE, SW V2.04 Control mode TQRPG Factory Setting: 0 Settings 0~100% 08-83 Friction Compe

Strany 97 - Auto Energy-saving Operation

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-137Group 9: Communication Parameters There is a built-in RS-485 se

Strany 98 - RUN STOP RUN STOP

Chapter 4 Parameters| 4-138 Revision August 2008, 03VE, SW V2.04 09-03 COM1 Time-out Detection Unit: 0.1Control mode VF VFPG SVC FOCPG TQRPG F

Strany 99

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-139Character ‘8’ ‘9’ ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’ ASCII code 38H

Strany 100

Chapter 4 Parameters| 4-140 Revision August 2008, 03VE, SW V2.04 DATA (n-1) to DATA 0 Contents of data: Nx8-bit data consist of 2n ASCII codes n<=

Strany 101

Chapter 1 Introduction| 1-10 Revision August 2008, 03VE, SW V2.04Frame B HW1DWH1D2D1S1S2 Unit: mm[inch] Frame W W1 H H1 D D1 D2 S1 S2 B1 1

Strany 102

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-141Command message: Response message: ‘0’ ‘1’ ‘2’ ‘7’ ‘0’

Strany 103

Chapter 4 Parameters| 4-142 Revision August 2008, 03VE, SW V2.04 00H 00H 17H 17H Data content 70H Data content 70H CRC CHK Low 86H CRC CHK L

Strany 104 - /f Curve

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-143content A0H CRC Check Low ‘9’ CRC Check High ‘A’

Strany 105 - 01-12,14,16,18,20

Chapter 4 Parameters| 4-144 Revision August 2008, 03VE, SW V2.04 transmitting the CRC value in the message, the upper and lower bytes of the CRC valu

Strany 106 - Frequency

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-145Content Address Function Bit 0 1: EF (external fault) on Bit

Strany 107 - Chapter 4 Parameters

Chapter 4 Parameters| 4-146 Revision August 2008, 03VE, SW V2.04 STX ‘:’ Address 01H ‘0’ Function 86H Address Low Address High ‘1’ Exception co

Strany 108 - REV:("OPEN": FWD)

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-147outportb(PORT+MCR,0x08); /* interrupt enable */ outpo

Strany 109

Chapter 4 Parameters| 4-148 Revision August 2008, 03VE, SW V2.04 2 Modbus ASCII mode, protocol <7,E,1> 3 Modbus ASCII mode, protocol

Strany 110

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-14909-14  Block Transfer 4 Unit: 109-15  Block Transfer 5 Uni

Strany 111

Chapter 4 Parameters| 4-150 Revision August 2008, 03VE, SW V2.04 Group 10 PID Control 10-00 Encoder Pulse Unit: 1Control mode VFPG FOCPG TQRPG

Strany 113

Chapter 1 Introduction| Revision August 2008, 03VE, SW V2.04 1-11Frame C H1HWW1DS1S2 Unit: mm[inch] Frame W W1 H H1 D -

Strany 114

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-151 10-02  PG Feedback Fault Treatment Control mode VFPG FOCPG TQR

Strany 115

Chapter 4 Parameters| 4-152 Revision August 2008, 03VE, SW V2.04  When integral time is set to 0, it is disabled. Pr.10-08 defines the switch frequ

Strany 116 - UP/DOWN Key Mode

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-153 Settings 0 to 50% (0: disable) 10-13 PG Slip Detection Time

Strany 117

Chapter 4 Parameters| 4-154 Revision August 2008, 03VE, SW V2.04 4 Phase A is a pulse input and phase B is a direction input. (low input=forward di

Strany 118

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-155 10-20 Range for PG Position Attained (Home range) Unit: 1Contr

Strany 119

Chapter 4 Parameters| 4-156 Revision August 2008, 03VE, SW V2.04 AUI +10VAUI 0VAUI -10V 0HzMax. output frequencyPr.01-00Resolution switch frequencyP

Strany 120

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-157PIIGBT &PWMM07-27TQ B i as10-0901-0101-0205-01~0910-0010-0

Strany 121

Chapter 4 Parameters| 4-158 Revision August 2008, 03VE, SW V2.04 RUNSTOPON OFFOFF ON03-00~03=2(AVI/AUI/ACIis torque command)RUN/STOPmulti-function in

Strany 122

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-159Group 11 Advanced Parameters 11-00  System Control Control mod

Strany 123 - VF VFPG SVC FOCPG TQRPG

Chapter 4 Parameters| 4-160 Revision August 2008, 03VE, SW V2.04 PIHz10-0610-0710-0410-0510-2110-220Hz10-085Hz 5HzPIHz11-0311-020Hz10-085Hz 5HzPI adj

Strany 124 - Terminal Count Value Unit:1

Chapter 1 Introduction| 1-12 Revision August 2008, 03VE, SW V2.04Frame D S1WW1HH1DD1D2 Unit: mm[inch] Frame W W1 H H1 D D1 D2 S1 - D 250.0

Strany 125 - [02-06=23]

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-161 After finishing estimating and set Pr.11-00=1 (auto tuning),

Strany 126 - RUN/STOP

Chapter 4 Parameters| 4-162 Revision August 2008, 03VE, SW V2.04 HzN-mFbase11-05/11 -06Flux Weakening Curve 11-06  Gain Value of Flux Weakening Cu

Strany 127

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-163Control mode FOCPG Factory Setting: 0 Settings 0 to 100

Strany 128

Chapter 4 Parameters| 4-164 Revision August 2008, 03VE, SW V2.04 Settings 0.001 to 65.535 Sec  It is used to lower the blinking frequency of LCD

Strany 129

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-165This page intentionally left blank

Strany 131

Revision August 2008, 03VE, SW V2.04 5-1 Chapter 5 Troubleshooting 5.1 Over Current (OC) ocAocdOC Over-current during acceleration

Strany 132

Chapter 5 Troubleshooting| 5-2 Revision August 2008, 03VE, SW V2.04 5.2 Ground Fault GFFGround faultNoYesIf output circuit(cable or motor) of AC mo

Strany 133

Chapter 5 Troubleshooting| Revision August 2008, 03VE, SW V2.04 5-35.4 Low Voltage (Lv) Low voltagePower cut, including momenta

Strany 134

Chapter 5 Troubleshooting| 5-4 Revision August 2008, 03VE, SW V2.04 5.5 Over Heat (oH1, oH2, oH3) AC motor drive overheatsHeat sink overheatsCheck i

Strany 135

Chapter 1 Introduction| Revision August 2008, 03VE, SW V2.04 1-13Frame E W1W DH1H2S2HD1S1D2S3 Unit: mm[inch] Frame W W1 H H

Strany 136

Chapter 5 Troubleshooting| Revision August 2008, 03VE, SW V2.04 5-55.7 Display of KPV-CE01 is Abnormal Abnormal display or no d

Strany 137

Chapter 5 Troubleshooting| 5-6 Revision August 2008, 03VE, SW V2.04 5.9 Motor cannot Run Motor cannot runCheck if CE01 displays normallyNoN

Strany 138

Chapter 5 Troubleshooting| Revision August 2008, 03VE, SW V2.04 5-75.10 Motor Speed cannot be Changed Motor can run bu

Strany 139 - Y-connection

Chapter 5 Troubleshooting| 5-8 Revision August 2008, 03VE, SW V2.04 5.11 Motor Stalls during Acceleration Motor stalls during accelerationCheck if ac

Strany 140

Chapter 5 Troubleshooting| Revision August 2008, 03VE, SW V2.04 5-95.13 Electromagnetic/Induction Noise There are many noises su

Strany 141

Chapter 5 Troubleshooting| 5-10 Revision August 2008, 03VE, SW V2.04 4. Store within a relative humidity range of 0% to 90% and non-condensing envir

Strany 142

Revision August 2008, 03VE, SW V2.04 6-1 Chapter 6 Fault Code Information and Maintenance 6.1 Fault Code Information The AC motor drive has a compre

Strany 143

Chapter 6 Fault Code Information and Maintenance| 6-2 Revision August 2008, 03VE, SW V2.04 Fault Name Fault Descriptions Corrective Actions Ground

Strany 144 - 30V(60V)

Chapter 6 Fault Code Information and Maintenance| Revision August 2008, 03VE, SW V2.04 6-3Fault Name Fault Descriptions Correc

Strany 145

Chapter 6 Fault Code Information and Maintenance| 6-4 Revision August 2008, 03VE, SW V2.04 Fault Name Fault Descriptions Corrective Actions Broken

Strany 146

Chapter 1 Introduction| 1-14 Revision August 2008, 03VE, SW V2.04This page intentionally left blank

Strany 147

Chapter 6 Fault Code Information and Maintenance| Revision August 2008, 03VE, SW V2.04 6-5Fault Name Fault Descriptions Correc

Strany 148 - Pr.06-08, 06-11

Chapter 6 Fault Code Information and Maintenance| 6-6 Revision August 2008, 03VE, SW V2.04 Fault Name Fault Descriptions Corrective Actions It wil

Strany 149 - 60Hz or more

Chapter 6 Fault Code Information and Maintenance| Revision August 2008, 03VE, SW V2.04 6-76.2 Maintenance and Inspections Modern

Strany 150

Chapter 6 Fault Code Information and Maintenance| 6-8 Revision August 2008, 03VE, SW V2.04 Periodical Maintenance  Ambient environment Maintenance

Strany 151

Chapter 6 Fault Code Information and Maintenance| Revision August 2008, 03VE, SW V2.04 6-9Maintenance Period Check Items Method

Strany 152

Chapter 6 Fault Code Information and Maintenance| 6-10 Revision August 2008, 03VE, SW V2.04  DC capacity of main circuit Maintenance Period Check I

Strany 153

Chapter 6 Fault Code Information and Maintenance| Revision August 2008, 03VE, SW V2.04 6-11 Printed circuit board and connecto

Strany 154

Chapter 6 Fault Code Information and Maintenance| 6-12 Revision August 2008, 03VE, SW V2.04 This page intentionally left blank

Strany 155

Revision August 2008, 03VE, SW V2.04 A-1 Appendix A Specifications Voltage

Strany 156

Appendix A Specifications| A-2 Revision August 2008, 03VE, SW V2.04 General Specifications Control System 1 V/f curve; 2 V/f+PG; 3 SVC; 4 FOC+PG;

Strany 157

Revision August 2008, 03VE, SW V2.04 2-1 Chapter 2 Installation and Wiring After removing the front cover (see chapter 1.2.3 for details), check if

Strany 158

Revision August 2008, 03VE, SW V2.04 B-1 Appendix B Accessories B.1 All Brake Resistors & Brake Units Used in AC Motor Drives Note: Please only

Strany 159

Appendix B Accessories| B-2 Revision August 2008, 03VE, SW V2.04 1. Please select the factory setting resistance value (Watt) and the duty-cycle va

Strany 160

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-3R/L1S/L2T/L3NFBMC VFD SeriesMOTORO.L.U/T1V/T2W/T3+P-N()()B1B2S

Strany 161

Appendix B Accessories| B-4 Revision August 2008, 03VE, SW V2.04 B.1.1 Dimensions and Weights for Brake Resistors (Dimensions are in millimeter) Or

Strany 162

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-5Order P/N: BR500W030, BR500W100, BR1KW020, BR1KW075 Model no.

Strany 163

Appendix B Accessories| B-6 Revision August 2008, 03VE, SW V2.04 Order P/N: BR1K0W050, BR1K2W008, BR1K2W6P8, BR1K5W005, BR1K5W040 B.1.2 Specificat

Strany 164

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-7B.1.3 Dimensions for Brake Unit (Dimensions are in millimeter[i

Strany 165

Appendix B Accessories| B-8 Revision August 2008, 03VE, SW V2.04 Figure 2: VFDB4132 VFDB4132CHARGE ACT OC OH

Strany 166

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-9B.2 No-fuse Circuit Breaker Chart For 3-phase drives, the curre

Strany 167

Appendix B Accessories| B-10 Revision August 2008, 03VE, SW V2.04 B.3 Fuse Specification Chart Smaller fuses than those shown in the table are permi

Strany 168

Chapter 2 Installation and Wiring| 2-2 Revision August 2008, 03VE, SW V2.042.1 Wiring Users must connect wires according to the circuit diagrams on

Strany 169 - Unit: 0.1

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-11B.4 AC Reactor B.4.1 AC Input Reactor Recommended Value 460V,

Strany 170 - Differential

Appendix B Accessories| B-12 Revision August 2008, 03VE, SW V2.04 Inductance (mH) kW HP Fundamental Amps Max. continuous Amps 3% impedance 5% impeda

Strany 171

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-13B.4.3 Applications for AC Reactor Connected in input circuit A

Strany 172 -

Appendix B Accessories| B-14 Revision August 2008, 03VE, SW V2.04 Correct wiring DCpowerreactorreactorAC motor drivemotorsilicon rectifier Applica

Strany 173 -  Line speed, speed mode

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-15B.5 Zero Phase Reactor (RF220X00A) Recommended Wire

Strany 174 -  Open-loop, torque mode

Appendix B Accessories| B-16 Revision August 2008, 03VE, SW V2.04 B.6 DC Choke Recommended Values 230V DC Choke Input voltage kW HP DC Amps Ind

Strany 175

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-17B.7 Remote Controller RC-01 Dimensions are in millimeter AFM

Strany 176

Appendix B Accessories| B-18 Revision August 2008, 03VE, SW V2.04 B.8 PG Card (for Encoder) B.8.1 EMV-PG01X AB2:PG2 signalmode switchABZ1:PG1 signal

Strany 177

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-19 Types of Pulse Generators Maximum Wire Length Wire Gauge Out

Strany 178

Appendix B Accessories| B-20 Revision August 2008, 03VE, SW V2.04 wiring 2 R/L1S/L2T/L3NFBRST+1+2/B1B2U/T1V/T2W/T3M3~-UWVVPDCMA1A1B1B1Z1Z1PGjumperBr

Strany 179

Chapter 2 Installation and Wiring| Revision August 2008, 03VE, SW V2.04 2-3Main circuit (power) terminalsControl circuit terminal

Strany 180

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-21ABZ1+ PS1 AB2+PS1 Types of Pulse Generators5V 12V 5V 12V L

Strany 181

Appendix B Accessories| B-22 Revision August 2008, 03VE, SW V2.04 Terminal Symbols Descriptions DCM Power source and input signal common A1, B1, Z1,

Strany 182

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-23wiring 1 R/L 1S/L2T/L3NFBRST+1+2/B1B2U/T1V/T2W/T3M3~-UWVVPDC M

Strany 183

Appendix B Accessories| B-24 Revision August 2008, 03VE, SW V2.04 5. Types of Pulse Generators (Encoders) ABZ1+PS1 AB2+PS1 Types of Pulse Generator

Strany 184

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-25B.8.3 EMV-PG01L PG OUTpulse outputAB2: PG2 signalmode switchAB

Strany 185

Appendix B Accessories| B-26 Revision August 2008, 03VE, SW V2.04 b. Recommended wire size 0.21 to 0.81mm2 (AWG24 to AWG18). 3. Wire length: (wire

Strany 186

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-27wiring 2 R/L1S/L2T/L3NFBRST+1+2/B1B2U/T1V/T2W/T3M3~-UWVVPDCMA1

Strany 187

Appendix B Accessories| B-28 Revision August 2008, 03VE, SW V2.04 ABZ1 AB2 Types of Pulse Generators 5V 5V Line driver QQ OCTP OCTP Complementary

Strany 188 - ( 7.E.1)

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-29B.9 AMD-EMI Filter Cross Reference AC Drives Model Number Fo

Strany 189

Appendix B Accessories| B-30 Revision August 2008, 03VE, SW V2.04 5. The cover of EMI filter and AC motor drive or grounding should be fixed on the

Strany 190

Chapter 2 Installation and Wiring| 2-4 Revision August 2008, 03VE, SW V2.04Figure 3 Wiring for SINK(NPN) mode and SOURCE(PNP) mode *Don't appl

Strany 191

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-31The length of motor cable When motor is driven by an AC motor

Strany 192

Appendix B Accessories| B-32 Revision August 2008, 03VE, SW V2.04  If the length is too long, the stray capacitance between cables will increase a

Strany 193

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-33B.9.1 Dimensions Dimensions are in millimeter and (inch) Order

Strany 194

Appendix B Accessories| B-34 Revision August 2008, 03VE, SW V2.04 Order P/N: RF022B21BA / RF037B43BA 3021101503155.5306030215 30

Strany 195

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-35Order P/N: RF110B43CA 603320012039838226203827.0

Strany 196

Appendix B Accessories| B-36 Revision August 2008, 03VE, SW V2.04 Order P/N: 10TDT1W4C Order P/N: 26TDT1W4C

Strany 197

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-37Order P/N: 50TDS4W4C Order P/N: 100TDS84C

Strany 198

Appendix B Accessories| B-38 Revision August 2008, 03VE, SW V2.04 Order P/N: 200TDDS84C Order P/N: 150TDS84C

Strany 199

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-39Order P/N: 180TDS84C

Strany 200

Appendix B Accessories| B-40 Revision August 2008, 03VE, SW V2.04 B.10 Multi-function I/O Extension Card B.10.1 Functions EMV-APP01 optional multi-f

Strany 201

Chapter 2 Installation and Wiring| Revision August 2008, 03VE, SW V2.04 2-5 MotorOutput AC Line ReactorPower SupplyMagneticcontac

Strany 202

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-41Terminals Description 5V Output power 500mA Max GND Analog

Strany 203

Appendix B Accessories| B-42 Revision August 2008, 03VE, SW V2.04 B.10.2 Dimensions B.10.3 Wiring Analog signal commonOutput powerrefer to Pr.02-2

Strany 204

Appendix B Accessories| Revision August 2008, 03VE, SW V2.04 B-43This page intentionally left blank

Strany 206 - TQ B i as

Revision August 2008, 03VE, SW V2.04 C-1 Appendix C How to Select the Right AC Motor Drive The choice of the right AC motor drive for the applicati

Strany 207

Appendix C How to Select the Right AC Motor Drive| C-2 Revision August 2008, 03VE, SW V2.04 1. When one AC motor drive operates one motor The starti

Strany 208 - FOCPG

Appendix C How to Select the Right AC Motor Drive| Revision August 2008, 03VE, SW V2.04 C-3 2.3 When it is running continuous

Strany 209

Appendix C How to Select the Right AC Motor Drive| C-4 Revision August 2008, 03VE, SW V2.04 Selection Note 1. When the AC Motor Drive is connected

Strany 210

Appendix C How to Select the Right AC Motor Drive| Revision August 2008, 03VE, SW V2.04 C-5 C.3 How to Choose a Suitable Moto

Strany 211 - Flux Weakening Curve

Appendix C How to Select the Right AC Motor Drive| C-6 Revision August 2008, 03VE, SW V2.04  Resonant mechanical vibration: anti-vibration (damping

Strany 212

Chapter 2 Installation and Wiring| 2-6 Revision August 2008, 03VE, SW V2.04 Figure 1 for the main terminals R(L1)S(L2)T(L3)RSTU(T1)V(T2)W(T3)IM3~MCE

Strany 213

Appendix C How to Select the Right AC Motor Drive| Revision August 2008, 03VE, SW V2.04 C-7 The torque characteristics of a m

Strany 214

Appendix C How to Select the Right AC Motor Drive| C-8 Revision August 2008, 03VE, SW V2.04 This page intentionally left blank.

Strany 216 - Chapter 5 Troubleshooting

Chapter 2 Installation and Wiring| Revision August 2008, 03VE, SW V2.04 2-7Mains power terminals (R/L1, S/L2, T/L3)  Connect th

Strany 217 - Troubleshooting

Chapter 2 Installation and Wiring| 2-8 Revision August 2008, 03VE, SW V2.04 To improve power factor and reduce harmonics connect a DC reactor betw

Strany 218 - 5.4 Low Voltage (Lv)

Chapter 2 Installation and Wiring| Revision August 2008, 03VE, SW V2.04 2-9 2.3.2 Main Circuit Terminals Frame B +1+2B1-B2U/T1 V/

Strany 219

Chapter 2 Installation and Wiring| 2-10 Revision August 2008, 03VE, SW V2.04Frame D 3V/T2W/T3R/L1DC DC + ( ) ( ) - POWER S/L2 T/L3-+2+1MOTORIM M

Strany 220 - 5.8 Phase Loss (PHL)

Chapter 2 Installation and Wiring| Revision August 2008, 03VE, SW V2.04 2-11+24SINK Modemulti-inputterminalInternal CircuitDCM

Strany 221

Chapter 2 Installation and Wiring| 2-12 Revision August 2008, 03VE, SW V2.04Terminal symbols and functions Terminal Symbol Terminal Function Factory

Strany 222

Chapter 2 Installation and Wiring| Revision August 2008, 03VE, SW V2.04 2-13Terminal Symbol Terminal Function Factory Settings (S

Strany 223

Chapter 2 Installation and Wiring| 2-14 Revision August 2008, 03VE, SW V2.04Terminal Symbol Terminal Function Factory Settings (SINK) ON: Connect to

Strany 224 - 5.14 Environmental Condition

Chapter 2 Installation and Wiring| Revision August 2008, 03VE, SW V2.04 2-15General  Keep control wiring as far as possible fro

Strany 226 - 6.1 Fault Code Information

Preface Thank you for choosing DELTA’s high-performance VFD-VE Series. The VFD-VE Series is manufactured with high-quality components and materials a

Strany 227

Revision August 2008, 03VE, SW V2.04 3-1 Chapter 3 Digital Keypad Operation and Start Up 3.1 Digital Keypad KPV-CE01 3.1.1 Description of the Digita

Strany 228

Chapter 3 Digital Keypad Operation and Start Up| 3-2 Revision August 2008, 03VE, SW V2.04Display Message Descriptions Displa

Strany 229

Chapter 3 Digital Keypad Operation and Start Up| Revision August 2008, 03VE, SW V2.04 3-33.1.2 How to Operate the Digital Keypa

Strany 230

Chapter 3 Digital Keypad Operation and Start Up| 3-4 Revision August 2008, 03VE, SW V2.04UFHUFHUFHUFHUFHUFHUFHUFHUFHUFHUFHUFHU

Strany 231 - 6.1.2 Reset

Chapter 3 Digital Keypad Operation and Start Up| Revision August 2008, 03VE, SW V2.04 3-53.1.3 Dimension of the Digital Keypad

Strany 232

Chapter 3 Digital Keypad Operation and Start Up| 3-6 Revision August 2008, 03VE, SW V2.043.1.5 Operation Method Refer to 3.1.2

Strany 233

Chapter 3 Digital Keypad Operation and Start Up| Revision August 2008, 03VE, SW V2.04 3-7Carefully check the following items be

Strany 234

Chapter 3 Digital Keypad Operation and Start Up| 3-8 Revision August 2008, 03VE, SW V2.043.2.2 Trial Run After finishing check

Strany 235

Chapter 3 Digital Keypad Operation and Start Up| Revision August 2008, 03VE, SW V2.04 3-9NOTE 1. Please stop running immediate

Strany 236

Chapter 3 Digital Keypad Operation and Start Up| 3-10 Revision August 2008, 03VE, SW V2.04This page intentionally left blank.

Strany 237

WARNING! 1. DO NOT use Hi-pot test for internal components. The semi-conductor used in AC motor drive easily damage by high-voltage. 2. There are h

Strany 238 - Appendix A Specifications

Revision August 2008, 03VE, SW V2.04 4-1 Chapter 4 Parameters The VFD-VE parameters are divided into 12 groups by property for easy setting. In most

Strany 239

Chapter 4 Parameters| 4-2 Revision August 2008, 03VE, SW V2.04 4.1 Summary of Parameter Settings : The parameter can be set during operation. Group

Strany 240 - Appendix B Accessories

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-3Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG

Strany 241 - Appendix B Accessories

Chapter 4 Parameters| 4-4 Revision August 2008, 03VE, SW V2.04 Group 1 Basic Parameters Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG T

Strany 242 - VFD Series

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-5Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG

Strany 243

Chapter 4 Parameters| 4-6 Revision August 2008, 03VE, SW V2.04 Group 2 Digital Input/Output Parameters Pr. Explanation Settings Factory SettingVF V

Strany 244

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-7Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG

Strany 245

Chapter 4 Parameters| 4-8 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG 44: Max. reel diam

Strany 246 - 130.0 [5.12]

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-9Group 3 Analog Input/Output Parameters Pr. Explanation Settings

Strany 247 - CHARGE ACT OC OH

Chapter 4 Parameters| 4-10 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory Setting VF VFPG SVC FOCPG TQRPG 9: AVI ○ ○ ○ ○

Strany 248

Table of Contents Preface ... i Table of C

Strany 249 - B.3 Fuse Specification Chart

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-11Group 4 Multi-Step Speed Parameters Pr. Explanation Settings Fa

Strany 250 - B.4 AC Reactor

Chapter 4 Parameters| 4-12 Revision August 2008, 03VE, SW V2.04 Group 5 Motor Parameters Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG

Strany 251

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-13Group 6 Protection Parameters Pr. Explanation Settings Factory

Strany 252

Chapter 4 Parameters| 4-14 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG 11: Low-voltag

Strany 253

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-15Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRP

Strany 254

Chapter 4 Parameters| 4-16 Revision August 2008, 03VE, SW V2.04 Group 7 Special Parameters Pr. Explanation Settings Factory SettingVF VFPG SVC FOC

Strany 255

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-17Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRP

Strany 256 - B.7 Remote Controller RC-01

Chapter 4 Parameters| 4-18 Revision August 2008, 03VE, SW V2.04 Group 8 High-function PID Parameters Pr. Explanation Settings Factory SettingVF VFP

Strany 257 - B.8.1 EMV-PG01X

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-19Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG

Strany 258

Chapter 4 Parameters| 4-20 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG 08-65 Error Treatme

Strany 259

2.4 Control Terminals ...2-10 Chapter 3 Digital Keypad Operation and Start

Strany 260 - B.8.2 EMV-PG01O

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-21Group 9 Communication Parameters Pr. Explanation Settings Facto

Strany 261

Chapter 4 Parameters| 4-22 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory Setting VF VFPG SVC FOCPG TQRPG 09-20 Block Tran

Strany 262 - EMV-PG01O

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-23Group 10 Speed Feedback Control Parameters Pr. Explanation Sett

Strany 263 - Complementary

Chapter 4 Parameters| 4-24 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory Setting VF VFPG SVC FOCPG TQRPG 10-21 P Gain of

Strany 264 - B.8.3 EMV-PG01L

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-25Group 11 Advanced Parameters Pr. Explanation Settings Factory S

Strany 265

Chapter 4 Parameters| 4-26 Revision August 2008, 03VE, SW V2.04 4.2 Version Differences 4.2.1 Version 2.02 New or update parameter groups are: Group

Strany 266

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-27Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG

Strany 267

Chapter 4 Parameters| 4-28 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG 4: Ground fault

Strany 268

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-29In version 2.02, the parameters are from Pr.08-00 to Pr.08-15. Pr

Strany 269

Chapter 4 Parameters| 4-30 Revision August 2008, 03VE, SW V2.04 New settings 44~50 for Pr.02-00~Pr.02-06 and new parameter 02-43. Pr. Explanation S

Strany 270

5.8 Phase Loss (PHL) ... 5-5 5.9 Motor cannot Run...

Strany 271

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-31Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG

Strany 272 - B.9.1 Dimensions

Chapter 4 Parameters| 4-32 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG 50: Reserved

Strany 273

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-33 Group 5 Motor Parameters Pr. Explanation Settings Factory Sett

Strany 274

Chapter 4 Parameters| 4-34 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG 39: Ground curr

Strany 275 - Order P/N: 26TDT1W4C

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-35Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG

Strany 276 - Order P/N: 100TDS84C

Chapter 4 Parameters| 4-36 Revision August 2008, 03VE, SW V2.04 Pr. Explanation Settings Factory SettingVF VFPG SVC FOCPG TQRPG Reel Diameter 1: E

Strany 277 - Order P/N: 150TDS84C

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-37Group 9 Communication Parameters Pr. Explanation Settings Facto

Strany 278 - Order P/N: 180TDS84C

Chapter 4 Parameters| 4-38 Revision August 2008, 03VE, SW V2.04 4.3 Description of Parameter Settings Group 0 User Parameters : This parameter can

Strany 279 - B.10.1 Functions

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-39 00-02 Parameter Reset Control mode VF VFPG SVC FOCPG TQRPG F

Strany 280 - Max: 48Vdc/50mA

Chapter 4 Parameters| 4-40 Revision August 2008, 03VE, SW V2.04 00-04 Content of Multi-Function function Display Settings 0 Display the output

Strany 281 - Output power

B.4.3 Applications for AC Reactor...B-13 B.5 Zero Phase Reactor (RF220X00A) ...

Strany 282

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-4100-04 Content of Multi-Function function Display 21 Number

Strany 283

Chapter 4 Parameters| 4-42 Revision August 2008, 03VE, SW V2.04 Control mode VF VFPG SVC FOCPG TQRPG Factory setting: 0 Settings Digit 4: decim

Strany 284 - C.1 Capacity Formulas

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-43Control mode VF VFPG SVC FOCPG TQRPG Factory setting: 00 Set

Strany 285

Chapter 4 Parameters| 4-44 Revision August 2008, 03VE, SW V2.04 00-09 Energy Saving Gain Unit: 1Control mode FOCPG Factory setting: 100% S

Strany 286 - )(_____103

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-45020 40 6080 10010090807060504030201001-02 voltage%01-01 Frequency

Strany 287

Chapter 4 Parameters| 4-46 Revision August 2008, 03VE, SW V2.04 When Pr.00-13 is set to 0.1201-0001-12 01-1401-1601-1801-13 01-1501-17 01-1901-0512Fr

Strany 288 - Load duty-cycle

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-47 From the table, we see that the PWM carrier frequency has a si

Strany 289

Chapter 4 Parameters| 4-48 Revision August 2008, 03VE, SW V2.04 75%100%Output VoltageThe maximum output voltagereduction is 25%.Auto Energy-saving Op

Strany 290

Chapter 4 Parameters| Revision August 2008, 03VE, SW V2.04 4-49 The parameter determines how the motor is stopped when the AC

Strany 291

Chapter 4 Parameters| 4-50 Revision August 2008, 03VE, SW V2.04 Group 1 Basic Parameters 01-00 Maximum Output Frequency Unit: 0.01Control mode VF VFP