Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
1-84 Revision January, 2008, Doc. Name: 2007PDD23000007
Mitsubishi Q Series Computer Link Back to Table
A. HMI factory settings
Baud rate: 19200, 8, None, 1.
Controller Station number: 0.
Control area/status area: D0 / D10.
NOTE
1) This communication protocol supports Q series RS232 communication module (QJ71C24-R2) and
RS422 communication protocol (QJ71C24N).
2) Before using this communication protocol, the user needs to set communication module via PC software ,
GX Developer. For more detailed information regarding the setting method, please refer to Mitsubishi
User Manual named “User’s Manual (Basic) - Q Corresponding Series Communication Module”.
B. Definition of controller Read/Write address
Registers
Read/Write Range
Register Type Format
Word No. Bit No.
Data length
Input Xn n: 0-1FFF N/A Word (multiple of 16)
Output Yn n: 0-1FFF N/A Word (multiple of 16)
Internal Relay Mn n: 0-8191 N/A Word (multiple of 16)
Special Internal Relay Mn n: 9000-9255 N/A Word (9000 + multiple of 16)
Link Relay Bn n: 0-1FFF N/A Word (multiple of 16)
Annunciator Fn n: 0-2047 N/A Word (multiple of 16)
Timer Value TNn n: 0-2047 N/A Word
Counter Value CNn n: 0-2047 N/A Word
Data Register Dn n: 0-8191 N/A Word
Special Data Register Dn n: 9000-9255 N/A Word
Link Register Wn n: 0-1FFF N/A Word
¾
Xn, Yn, Bn, Wn : n is in hexadecimal.
Contacts
Read/Write Range
Contact type Format
Word No. Bit No.
Input Xn N/A n: 0-1FFF
Output Yn N/A n: 0-1FFF
Internal Relay Mn N/A n: 0-8191
Special Internal Relay Mn N/A n: 9000-9255