VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-8
Parameters Functions Settings
Factory
Setting
Customer
37: PLC program operation
Paused
38: Loss of an ACI signal
indication
39: HOA-Hand mode indication
40: HOA-Off mode indication
41: HOA-Auto mode indication
42: Fire mode indication
43: Bypass fire mode indication
03-08 Master Frequency Attained 1 0.00~120.00 Hz 0.00
03-09 Master Frequency Attained 2 0.00~120.00 Hz 0.00
03-10 Analog Output 1, (AFM1)
0~10Vdc
00
03-11 Analog Output 2, (AFM2)
0/4~ 20mA
00: Output frequency
01: Output current
02: Output voltage
03: Frequency command
04: Power factor loading
01
03-12 Analog Output Gain 1 01~200%
100
03-13 Analog Output Gain 2 01~200%
100
03-14 Analog Output 2 Selection (AFM2
Definition)
00: 0~20mA
01: 4~20mA
01
03-15 DC Fan Control 00: Fan runs on power up.
01: Fan begins upon a RUN
command. Fan stops 1
minute after a STOP
command.
02: Fan begins upon a RUN
command. Fan stops after a
STOP command
03: Fan is controlled by
temperature.
Approximately a 60°C
temperature will start the fan.
04: Unusual fan status warning,
inverter continues to run.
(Setting 04 is only available in the
existing firmware v.3.104,
the new released version v.1.302
and the versions above v.1.302)
00