Chapter 4 Parameters|
4-20 Revision August 2008, 2ELE, V1.02
Parameter Explanation Settings
Factory
Setting
Custome
r
10.20
Treatment of the
Erroneous PID
Feedback Level
0: Keep operating
1: Coast to stop
2: Ramp to stop
3: Ramp to stop and restart after time set in
Pr.10.21
0
10.21
Restart Delay Time
after Erroneous PID
Deviation Level
1 to 9999 sec 60
10.22
Set Point Deviation
Level
0 to 100% 0
10.23
Detection Time of
Set Point Deviation
Level
0 to 9999 sec 10
10.24
Offset Level of
Liquid Leakage
0 to 50% 0
10.25
Liquid Leakage
Change Detection
0 to 100% (0: disable) 0
10.26
Time Setting for
Liquid Leakage
Change
0.1 to 10.0 sec (0: disable) 0.5
10.27
|
10.33
Reserved