VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
B-12
B.7 Zero Phase Reactor (RF220X00A)
Recommended Wire Size
Cable type
(Note)
AWG mm
2
Nominal
(mm2)
Qty. Wiring Method
≦10 ≦5.3 ≦5.5
1 Diagram A
Single-core
≦2 ≦33.6 ≦38
4 Diagram B
≦12 ≦3.3 ≦3.5
1 Diagram A
Three-core
≦1 ≦42.4 ≦50
4 Diagram B
Note: 600V Insulated Unshielded Cable.
Diagram A
Please wind each wire 4 times around the core. The reactor must be put at inverter side as
close as possible.
Power
Supply
Zero Phase Reactor
MOTOR
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Diagram B
Please put all wires through 4 cores in series without winding.
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Power
Supply
Zero Phase Reactor
MOTOR
Note1: The table above gives approximate wire size for the zero phase reactors but the
selection is ultimately governed by the type and diameter of cable fitted i.e. the cable
must fit through the center hole of zero phase reactors.
Note2: Only the phase conductors should pass through, not the earth core or screen.
Note3: When long motor output cables are used an output zero phase reactor may be
required to reduce radiated emissions from the cable.
UNIT: mm(inch)