Delta Electronics AC Motor Drive VFD-VE Series Specifikace Strana 74

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 182
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 73
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-46
5.7 Group 6: Protection Parameter
06-00 Low Voltage Level
Settings 160~220V
a
Factory setting 180
360~440V
a
Factory setting 360
This parameter determines the level for “LV” fault.
LV
06-00
15V
Input voltage
06-01 Over-Voltage Stall Prevention
Settings 350.0~450.0V
a
Factory setting 380.0
700.0~900.0V
a
Factory setting 760.0
This parameter sets the voltage limit for use with the Over Voltage Stall prevention
function. During deceleration, a heavy loaded motor will begin to regenerate voltage
back to the drive. As the drive absorbs this regenerated voltage the DC bus will
increase. If the DC bus reaches the value programmed in this parameter, the drive will
stop deceleration, hold speed, and wait for the power to dissipate, before deceleration
begins again.
*Twice the voltage for the 460V model
Over-Voltage Stall Prevention
,
properties of decel when the
function is activated.Output
Frequency
Frequency sustained
Pre-set
Deceleration
Time
Time
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Zobrazit stránku 73
1 2 ... 69 70 71 72 73 74 75 76 77 78 79 ... 181 182

Komentáře k této Příručce

Žádné komentáře