Delta Electronics RTU-EN01 Uživatelský manuál Strana 10

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 62
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 9
Ethernet Communication Module DVPEN01-SL
4.2 Explanations on CR
CR#0: Model code
Explanations:
1. Model code of DVPEN01-SL=H’4050.
2. You can read the model code in the program to see if the I/O module exists.
CR#1: Firmware version
Explanations:
The firmware version of DVPEN01-SL is displayed in hex, e.g. H’0100 indicates version V1.00.
CR#2: Communication mode
Explanations:
Bit No. Mode “0” “1”
b0 MODBUS TCP Disable Enable
b1 Data exchange Disable Enable
E-mail Functions
CR#3~6: E-mail event 1~4 trigger
Explanations:
When the CR is set as “1”, E-mail sending will be enabled. After the sending is completed, the CR will automatically be
reset as “0”. Note: Please trigger by differential instructions.
CR#7~8: Status of E-mail 1~4
Explanations:
1. CR#7_b0~b7: current status of E-mail 2; CR#7_b8~b15: current status of E-mail 1.
2. CR#8_b0~b7: current status of E-mail 4; CR#8_b8~b15: current status of E-mail 3.
3. Table of E-mail statuses
CR value E-mail status
0 Not been sent
1 Being processed
2 The sending of the E-mail is successful.
10 Fail to connect to the SMTP server.
11 Incorrect recipient E-mail address
12 SMTP server communication error
13 Exceeding the max. number of TCP connection
3~9, 14~255 Reserved
CR#9~12: E-mail 1~4 additional message
Explanations:
The user fills in the code, and the code will be stored in the title of the E-mail and sent out with the E-mail.
DVP-PLC Operation Manual