Ethernet Communication Module DVPEN01-SL
CR#16: Connection status of the RTU mapping slave
Explanations:
b3~b0 display the connection status of RTU slave. The connection may encounter some problems when any of the bits
becomes 0. Firmware V2.0 and later versions support RTU mapping.
b0: Status of RTU slave 1
b1: Status of RTU slave 2
b2: Status of RTU slave 3
b3: Status of RTU slave 4
4.3 Numbering of Left-Side Modules
After DVPEN01-SL is installed properly, you need to compile the PLC program to control the special I/O module. PLC
offers FROM instruction (for reading) and TO instruction (for writing) to control the control registers (CR) in the special
I/O module.
Numbering of the modules: Every special I/O module connected to PLC MPU has a No. to allow you to know which
module is which when compiling the PLC program. The first special I/O module attached at the left hand side of the
PLC MPU is numbered as K100, the second as K101, the third K102, and so on.
5 Setting the Software
This section gives instructions on how to set DVPEN01-SL by DCISoft and explanations on each setup page. Before
you start a setup page, you have to select Ethernet in the Communication Setting window. Next, you can search by
IP address or use Auto-Search. You also can open the setup page for DVPEN01-SL by RS-232. DVPEN01-SL is set by
UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall.
5.1 Setting Communication & Searching for Modules
Communication settings
1. Open DCISoft in your PC and click on Communication Setting.
DVP-PLC Operation Manual
14