! Function Explanations:
d 0 Not Used.
d 1 AC drive operational: the output terminal will be activated when the drive is running.
d 2 Maximum Output Frequency Attained: the output will be activated when the AC drive
attains Maximum Output Frequency.
d 3 Zero speed: the output will be activated when Command Frequency is lower than the
Minimum Output Frequency.
d 4 Over-Torque Detection: the output will be activated as long as the over-torque is
detected. Pr.6-04 determines the Over-Torque detection level.
d 5 Base-Block (B.B.) Indication: the output will be activated when the output of the AC
drive is shut off by external Baseblock.
d 6
Low Voltage Indication:
the output will be activated when low voltage is detected.
d 7 AC Drive Operation Mode: the output will be activated when the operation of the AC
drive is controlled by External Control Terminals.
d 8 Fault Indication: the output will be activated when faults occur (oc, ov, oH, oL, oL1, EF,
cF3, HPF, ocA, ocd, ocn, GF).
d 9 Desired Frequency Attained: the output will be activated when the desired frequency
(Pr.3-02)is attained.
d10 PLC Program Running: the output will be activated when the PLC program is running.
d11 PLC Program Step Completed: the output will be activated for 0.5 sec. when each
multi-step speed is attained.
d12 PLC Program completed: the output will be activated for 0.5 sec. when the PLC
program cycle has completed.
d13 PLC Program Operation Paused: the output will be activated when PLC operation is
paused.
d14 Terminal Count Value Attained: counter reaches Terminal Count Value.
d15 Preliminary Count Value Attained: counter reaches Preliminary Count Value.
d16 Ready State Indicator.
d17 FWD command indication: When AC drive receives the command of forward
running, it will output immediately no matter AC drive is in the state of run or stop.
d18 REV command indication: When AC drive receives the command of reverse
running, it will output immediately no matter AC drive is in the state of run or stop.