VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-42
5.9 Group 8: Special Parameters
8 - 00 DC Fékezési feszültségi szint Factory Setting: d 0
Settings d 0 to d30% Unit: 1%
! This parameter determines the level of DC Braking Voltage Level output to the motor
during start-up and stopping. When setting DC Braking Voltage, the Maximum Output
Voltage (Pr.1-02) is regarded as 100%. It is recommended to start with a low DC Braking
Voltage Level and then increase until proper holding torque has been attained.
8 - 01 DC Fékezési ideje indításnál Factory Setting: d 0.0
Settings d 0.0 to d 60.0 sec Unit: 0.1sec
! This parameter determines the duration of time that the DC Braking Current will be
applied to the motor during the AC drive start-up.
8 - 02 DC Fékezési idő a megállás során Factory Setting: d 0.0
Settings d 0.0 to d 60.0 sec Unit: 0.1 sec
! This parameter determines the duration of time that the DC braking voltage will be
applied to the motor during stopping. If stopping with DC Braking is desired, then
Pr.2-02 must be set to RAMP stop (d 0).
8 - 03
DC fékezés indítási pontja
Factory Setting: d 0.0
Settings d 0.0 to d 400Hz Unit: 0.1Hz
! This parameter determines the frequency when DC Braking will begin during
deceleration.
Operation
Command
ON
OFF
01-05
08-03
Output Frequency
Minimum Output
Frequency
Start-Point for
DC Braking
Time during
Stopping
DC Braking Voltage %
Time
08-01
08-02
NOTE: 1. DC Braking during Start-up is used for loads that may move before AC drive
starts, such as fans and pumps. These loads may also be moving in the wrong
direction. Under such circumstances, DC Braking can be executed to hold the
load in position before applying a forward motion.