Train ing Kit O peratio n Manua l
1-8
Mixed digital/analog
(D/A) module
Voltage output Current output
Communication
mode
(RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of
4,800/9,600/19,200/38,400 /57,600/115,200. For ASCII mode, date
format is 7 bits, even, 1 stop bit (7, E, 1). For RTU mode, date format is
8 bits, even, 1 stop bit (8, E, 1). The RS-485 is disabled when the
DVP06XA-S is connected in series with MPU.
Connect to
DVP-PLC MPU
in series
When DVP06XA-S modules are connected to an MPU, the modules are
numbered from 0-7. 0 is the closest to the MPU and 7 is the furthest.
The Maximum number of modules is 8 modules and they do not occupy
any digital I/O points of the MPU.
Mode 0: (0 V~+10 V); Mode 1: (2 V~+10 V)
Voltage output
Digital input
Mode 0
Mode 1
10V
+40 00
0
OFF SET
6V
5V
2V
GAIN
+20 00
Conversion Curve
(Default setting:
Mode 0)
Mode 2: (4 mA~+20 mA); Mode 3: (0 mA~+20 mA)
Current output
Digital input
Mode 3
Mode 2
20mA
+40 00
0
OFF SET
4mA
GAIN
+20 00
12mA
10mA
3. Other specifications
Power supply
Maximum power
consumption
2 W at 24VDC (20.4 V DC~28.8 V DC) (-
15%~+20%), supplied by external
power
Environment
Operation/storage
Operation: 0°C~5C (temperature); 50~95% (humidity); pollution degree 2
Storage: -25°C~70°C (temperature); 5~95% (humidity)
Vibration/shock
immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-
2 &
IEC 68-2-27 (TEST Ea)
Zobrazit stránku 10