Chapt er 1 Intr oduction of PLCs
1-9
1.6 Introdunction of DVP04PT-S
1. Introduction
DVP04PT-S is able to receive 4 points of platinum temperature sensors and convert them into
16-bit digital signals. Besides, through FROM/TO instructions in DVP Slim series MPU program,
the data in DVP04PT-S can be read and written. There are many 16-bit control registers (CR) in
DVP04PT-S. The power unit is separate from it and is small in size and easy to install.
2. Specifications
DVP04PT-S Celsius (°C) Fahrenheit (°F)
Power supply
voltage
24 V DC (20.4V DC~28.8 V DC) (-15%~+20%)
Analog input
channel
4 channels per module
Sensors type
2-wire/3-wire PT100/Ni100/PT1000/Ni100 3850 PPM/°C (DIN 43760 JIS
C1604-1989)
Current excitation
1.53 mA/204.8 uA
Temperature input
range
-200°C~600°C -328°F~1112°F
Digital conversion
range
K-2000~K6000 K-3280~K11120
Resolution
16 bits (0.1°C) 16 bits (0.1°F)
Overall accuracy
±
0.6% of full scale during 0 ~ 55°C (32 ~ 131°F)
Response time
200 ms × channels
Isolation method
Isolation between digital and analog circuitry. There is no isolation between
channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Digital data format
2’s complement of 16-bit
Average function
Yes (CR#2~CR#5)
Self diagnostic
function
Upper bound and lower bound detection per channel
Communication
mode
(RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of
4,800/9,600/19,200/38,400 /57,600/115,200. For ASCII mode, date format
is 7 bits, even, 1 stop bit (7, E, 1). For RTU mode, date format is 8 bits,
even, 1 stop bit (8, E, 1). The RS-485 is disabled when the DVP04PT-S is
connected in series with MPU.
Connect to
DVP-PLC MPU in
series
When DVP04PT-
S modules are connected to an MPU, the modules are
numbered from 0-7. 0 is the close
st to the MPU and 7 is the furthest. The
Maximum number of modules is 8 modules and they do not occupy any
digital I/O points of the MPU.