1.5 Introduction of DVP06XA-S
1. Introduction
DVP06XA-S is able to receive 4 points of analog input signals (voltage or current) and
convert them into 12-bit digital signals. DVP06XA-S receives 2 groups of 12-bit digital data
from the PLC MPU and converts them into 2 points of analog signals for output (in
voltage/current). There are 49 16-bit control registers (CR) in DVP06XA-S, and the data in it
can be read and written by using FROM/TO instructions in DVP Slim series PLC MPU
program.
The system version of DVP06XA-S can be updated via RS-485 communication. The power
unit is separate from it and is small in size and easy to install.
The user can select voltage or current input by wiring. Range of voltage input: 10 V DC
(resolution: 5 mV). Range of current input: 20 mA (resolution: 20 µA).
The user can also select voltage or current output by wiring. Range of voltage output: 0
V~+10 V DC (resolution: 2.5mV). Range of current output: 0 mA~20 mA (resolution: 5 µA).
2. Specifications
Mixed analog/digital
(A/D) module
Voltage input Current input
Power supply
voltage
24 V DC (20.4 V DC~28.8 V DC) (–15%~+20%)
Analog input
channel
4 channels per module
Analog input range
±10 V ±20 mA
Digital data range
±2,000 ±1,000
Resolution
12 bits(1
LSB
=5 mV) 11 bits (1
LSB
=20 µA)
Input impedance
200 kΩ and above 250 Ω
Overall accuracy
±0.5% of full scale of 25°C (77°F)
±1% of full scale during 0~55°C (32~131°F)
Response time
3 ms × channels
Isolation method
There is no isolation between channels
Absolution input
range
±15 V ±32 mA
Digital data format
2’s complement of 16-bit, (11 significant bits)
Average function
Yes (CR#2~CR#5 can be set and the range is K1~K4,096)
Self diagnostic
function
Upper bound and lower bound detection per channel